4th Generation Data Centers: Containerized Data Centers

Industry Trends News, 2020.4.26

Prepared By: Mark Rauchwarter

The 4th generation of data centers is emerging, bringing with it a radical redesign from its predecessors. Self-contained containers now allow for modularity and contain the necessary core components that enable this new design to function. This paper discusses advancements in data center management and the changes in technology and business goals that have driven the evolution of data centers into their 4th generation.

It also takes a closer look at containerized data center solutions and how their integration into the data center environment provides businesses with improved value.

Table of Contents

  • Abstract
  • Introduction
  • Brief History of Data Centers
  • 1st Generation
  • 2nd Generation
  • 3rd Generation
  • 4th Generation Data Center Design
  • Modularity
  • Energy Efficiency
  • Cooling Systems
  • Containerized Infrastructure Solutions
  • Server Configuration
  • Networking
  • Power
  • Cooling
  • Procurement Considerations
  • Additional Considerations
  • The Future of Data Centers
  • Conclusion
  • Bibliography

Introduction

New data centers are expected to have a life expectancy of 10, 20, or even 30 years or longer. However, technology has changed drastically over the past 10 years, prompting businesses to place greater demands on their data centers. Historically, data centers were purpose-built computer rooms housing mainframes and a handful of servers. The core focus has shifted from mainframes to servers, and further toward fully virtualized data centers running across a combination of hardware.

Along the way, businesses have continued to push for doing more with less. At a time when global economic hardships have been a common theme in recent history, all initiatives have focused on saving as much money as possible.

Brief History of Data Centers

Data centers have changed significantly over time. Until recently, most data centers remained static, with racks of servers in highly temperature-controlled, raised-floor environments. They generally adopted a traditional approach to data center management that had proven reliable over the years.

Within the past two decades, the industry has shifted its approach to data center management to provide the greatest value to the businesses it supports. This has led to generational segmentation, with each generation building upon its predecessor and further advancing data center design, operational procedures, and the technology utilized.

1st Generation

The first generation of data center design lasted for many years and remained relatively similar to the original purpose-built computer rooms of the mid-1900s. According to Manos, "these facilities focused more around uptime, reliability and redundancy. Big infrastructure was held accountable to solve all potential environmental shortfalls." (Manos, 2008) For many data centers, these are still their primary operational design principles, and they continue to function as 1st generation data centers today.

2nd Generation

Second-generation data centers started to emerge when it became clear that first-generation data centers were quickly becoming outdated and unable to keep up with the demands of technological developments, environmental concerns, and the marketplace.

These facilities took a closer look at and incorporated options to improve energy efficiency, sustainability, and total operating costs. They focused more on overall costs rather than just the initial upfront costs at the time of construction.

3rd Generation

Third-generation data centers have only recently been brought into operation, and some continue to be designed and built instead of adopting fourth-generation designs. This generation focuses on improving operating costs by placing even greater emphasis on energy efficiency and beginning to incorporate modularity into data center designs.

Modularity allows data centers to scale more easily to match market conditions and business needs by making smaller increases or decreases to their infrastructure.

4th Generation Data Center Design

As data centers continue along their evolutionary path, the industry is beginning to embrace what is known as the fourth generation of data center design. This generational advancement further builds on its predecessors by continuing to focus on the core aspects that ultimately lead to reduced overall capital expenditures and improved cost efficiency.

This includes further advancing modularity to allow for increased scalability and energy efficiency while reducing operational and maintenance requirements. Manos summarizes the promise of fourth-generation design as "a highly modular, scalable, efficient, just-in-time data center capacity program that can be delivered anywhere in the world very quickly and cheaply, while allowing for continued growth as required." (Manos, 2008)

Modularity

Modularity is one of the key themes of fourth-generation data center design. It allows data centers to scale more easily to meet business needs. With a modular data center, costs can be managed more effectively throughout its lifetime, and the facility can respond to market fluctuations and changing computing requirements. Modular units can be added or removed more easily and cost-effectively than constructing traditional data center buildings.

"Modular data centers reached prominence in 2007, [and] are now offered by many suppliers, and being deployed by utility-scale data center operators such as Microsoft and Google and in smaller installations throughout the industry." (Coles, 2011)

Information Technology (IT) infrastructure manufacturers have responded by providing a variety of self-contained modular units, sometimes housed in shipping containers. These units can further reduce costs by incorporating cooling and backup power systems appropriately sized for each module. This eliminates the need for extensive centralized infrastructure beyond network connectivity and primary power connections.

Some data centers currently under development have fully embraced modularity in their fourth-generation designs, including Microsoft.

In Microsoft's design, the flexibility provided by containerized servers will be applied across the entire facility, which will be constructed entirely "of modular units of prefabricated mechanical, electrical, security components, etc., in addition to containerized servers." (Manos, 2008) This means that no building needs to be constructed to house these modular units. Instead, they will be installed outdoors and connected directly to the core infrastructure not already contained within the modular units.

Energy Efficiency

Another key component of fourth-generation data center design is an ongoing focus on improving energy efficiency. As energy costs continue to rise worldwide, more companies and industries are looking for ways to reduce these expenses. Additionally, with a greater focus on green initiatives, such as reducing carbon emissions, data centers have become a critical focal point because they are among the primary facilities responsible for significant power consumption.

According to IBM, "with the cost of energy on the increase, we estimate that data centers use 30 to 80 times the energy of an office building per square foot (or square meter). This means that energy can represent 70 percent of the operational cost of a data center." (IBM, 2011)

Cooling Systems

Cooling system requirements go hand in hand with improving energy efficiency within data centers. Improved cooling techniques and methodologies help reduce energy costs even further.

Several data center facilities have embraced this concept by allowing IT equipment to operate at higher temperatures than in previous generations of data centers. The latest technology has been designed to allow equipment to run at increased temperatures without causing significant component damage or performance issues. This reduces cooling-related operating costs because the environment can remain warmer, meaning cooling units do not need to operate as frequently.

In some cases, if a data center is located in a temperate or cooler climate zone, outside air can be used alone without any supplemental cooling system. This provides the greatest energy efficiency, as measured by PUE (Power Usage Effectiveness, defined as Total Facility Power / IT Power). (Coles, 2011)

Containerized Infrastructure Solutions

Self-contained modular data center units have entered the marketplace over the past 5 to 10 years. These units vary considerably in terms of the components and options they contain, depending on customer requirements.

These modular units can be as simple as structures housing only racks of servers, requiring external connections for power, backup power, cooling and ventilation, and network connectivity. At the other end of the spectrum, they can contain all necessary components, including backup power and cooling, requiring only connections to primary power and WAN (Wide Area Network) connectivity.

Modularity

Figure 1 - A Chicago-Area Data Center Featuring Stacked Container Units (Coles, 2011)

Containerized solutions come in a variety of sizes. Some are housed in 10-, 20-, or 40-foot shipping containers, while others are purpose-built structures that still provide modularity on a scale comparable to shipping containers.

These prefabricated structures help data centers and businesses manage costs more easily by providing a clearly defined initial purchase price and calculable ongoing operating costs. Many units are designed to sit directly outdoors and therefore require only the necessary external connections for power, network connectivity, and possibly cooling if these systems are not self-contained.

As a result, no building or raised floor is required. The self-contained, prefabricated units also reduce the time needed to move from purchase to operation. While a traditional brick-and-mortar facility may take months or even years to become operational, these units can be shipped and brought online within weeks or months. In some cases, this significantly reduces overall initial implementation and construction costs.

According to a study conducted by Hewlett-Packard (HP), a typical brick-and-mortar data center was constructed at a total cost of $58,000,000.

The equivalent modular data center through the HP Flexible DC program cost only $28,000,000, resulting in a 55% reduction in initial capital development costs. (HP, 2010)

Server Configuration

Within these containerized solutions, a range of server configurations is available. These configurations range from several hundred servers to several thousand servers, depending on customer needs or the deployment scenario. Server types also vary in size, from full-rack and half-rack options to blade server designs.

Figure 2 - HP's POD Unit Featuring a Single Row of IT Rack Space. Cooling Design Uses Overhead Water-Cooled Coils (Coles, 2011)

An inherent issue with these containerized solutions, however, is their limited space. This can make maintenance and physical configuration changes difficult for technicians. One approach to addressing this issue is to continue using only systems that function properly and take malfunctioning systems offline until the container is replaced.

Any decision to adopt this approach needs to be carefully discussed and evaluated to determine which option may present the greatest risk of additional costs.

Networking

Figure 3 - Oracle Sun Modular Data Center, Featuring a Unique IT Rack Layout (Coles, 2011)

In nearly all containerized solutions, networking is included as part of the prefabricated unit. A primary reason is that cable management can become an issue in such a confined space.

Cables and wiring must be properly managed to make efficient use of the available space. Standard networking equipment can be used, but the fastest available options are often preferred, including fiber or 10-Gigabit connections, to achieve optimal data center performance.

Power

There are multiple power options for containerized solutions. Depending on the size of the unit, the power configuration can determine the container's connection requirements. Units can be configured for hard-wired stationary installations or quick-disconnect installations, depending on what is most appropriate or supported by the vendor.

Some units also include integrated backup power solutions. Uninterruptible Power Supplies (UPS) can be installed at the rack level "that can provide sufficient hold-up time for an automatic switch-over from the primary to secondary power source." (SGI, 2011)

The UPS can also be integrated into the entire container. Power distribution systems used when a UPS is incorporated into the container can further improve energy efficiency by reducing the amount of AC-to-DC power conversion and removing components between the utility supply and the server. (HP, 2010)

This can be achieved by removing the power supplies from individual servers and connecting DC power directly from the UPS to the servers and networking equipment.

Cooling

Containerized data center units offer the option of including or excluding cooling systems. When cooling is not included in the self-contained unit, an external source is required. This is typically provided through an external connection or an attachable modular cooling system, sometimes supplied by the same vendor.

The most common solutions on the market, however, appear to be units that include the necessary cooling systems. These systems offer various standard cooling options, including conventional hot- and cold-aisle configurations or water and/or refrigerant cooling systems attached directly to the racks within the enclosure.

Each option represents a different level of energy efficiency. M. Bramfitt and H. Coles conducted an analysis comparing different vendors that offered cooling system options for their containerized units. Figure 4 presents a breakdown of the results.

The results show that a Free Air system, which uses only outside air to cool the container without any additional cooling equipment, provides the best PUE. (Coles, 2011)

Figure 4

In the previously mentioned example of Microsoft's fourth-generation data center, the facility will use either an air-side economizer or a water-side economizer. This allows Microsoft to operate its facility flexibly and determine whether certain containers are more critical than others, as well as whether one cooling method is better suited to a particular situation.

These options also provide the lowest PUE values, resulting in the greatest energy efficiency.

Procurement Considerations

Purchasing a modular data center unit requires a complete understanding of the environment and the intended future goals of the data center. For many organizations, a containerized unit represents a significant capital expenditure, and the wide variety of market options can make selecting the right unit difficult.

Bramfitt and Coles provide a comprehensive list of items that should be documented and considered before and during the vendor selection process:

Before Engaging with a Vendor

  • Required initial and future rack space.
  • Required initial, average, and future maximum IT power per rack in each module, if multiple modules will be needed.
  • Detailed list of IT equipment required for each rack.
  • Allowable maximum IT equipment inlet air temperature.
  • Minimum and maximum IT equipment cooling air exit temperature.
  • IT equipment airflow type (e.g., side entry or front-to-back).
  • Required power connections per rack, i.e., single or redundant power input.

Selecting Cooling Technology

  • Tower chilled water.
  • Water-cooled chiller combined with tower chilled water.
  • Air-cooled chiller.
  • DX compressor cooling.

Topics to Review with Potential Modular and IT Equipment Suppliers

  • For cooling systems requiring chilled water: the highest possible chilled-water temperature that will meet IT air inlet temperature requirements.
  • Humidity controls and requirements.
  • Energy required for IT equipment cooling air circulation provided by the modular system. This should be in the range of 2% to 4% of IT power.
  • Cooling fluid pumping energy.
  • Modular enclosure heat insulation specifications.
  • Removal of cooling fans inside IT equipment.
  • IT equipment DC power.
  • Part-load energy efficiency and controls.

Additional Requirements

  • Service availability. Some cooling designs may contain materials that are difficult to obtain for repairs, such as fans or specialized coolants, or may require specialized tools or specific training. For example, timely temporary repairs to water-based cooling systems may be easier for on-site personnel than repairs to refrigerant-based systems that require specialists trained in refrigerant handling.
  • Service access to the unit, including clearances for connections, door openings, weather protection, and IT equipment installation.
  • Site security, including lighting, fencing, and access control.
  • Proximity to existing power and chilled-water distribution systems, if used.
  • Backup power equipment, if desired, including generators, switchgear, and fuel supply.
  • Control and reporting systems for modular units should be compatible with existing building management systems.
  • Check whether software is available for monitoring energy use or calculating energy efficiency metrics.
  • Smoke detection and fire suppression systems, including interconnection with existing systems if present.
  • Site access for delivery and placement, maximum allowable weight, and space for crane operations during unloading.
  • Module orientation relative to prevailing wind direction may be important for units equipped with air-side economizers (outside-air cooling) to achieve maximum energy efficiency.
  • Pad requirements. Modular/container units often require significant foundation or pad upgrades.
  • Condensation management. Local authorities may not permit condensate drains to be connected directly to sanitary sewer systems without a permit.
  • Emergency power-off functionality may be required by fire protection services.
  • Local authorities having jurisdiction should be consulted to determine agency requirements, applicable building and safety codes, and tax treatment, if applicable. (Coles, 2011)

Additional Considerations

Although containerized data centers are emerging as a potential future direction for the industry, several significant concerns should be considered before deciding whether a containerized data center is the right solution for a particular situation.

John Edwards identifies what he considers the primary disadvantages of modular data centers:

  • Durability: It remains uncertain how well pod-based and prefabricated modular data centers will withstand the effects of time and weather.
  • Service availability: Providing utility and network resources to pods and prefabricated units located in remote areas can be difficult and expensive.
  • Lack of workspace: Most modular facilities, particularly pods, are designed to accommodate equipment rather than people.
  • Vendor lock-in: Many modular data center solutions require adopters to commit to a vendor's hardware and/or support services.
  • Security: An isolated pod or prefabricated unit may be easier to break into or vandalize than a conventional building. (Edwards, 2011)

A modular design may not always be the best fit. Although the benefits are relatively clear when building a new, large data center, some organizations may be better suited to a more traditional data center.

Similarly, Edwards writes, "an existing facility - already bought and paid for - may be able to be more densely populated, making it a better financial bet than adding a modular unit." (Edwards, 2011)

The Future of Data Centers

The concepts behind fourth-generation data centers have the potential to revolutionize how people think about data centers. The idea of a large, cold room filled with server racks on a raised floor may soon become a thing of the past. The concept of modularity, which enables greater scalability, has attracted considerable interest across the industry.

Improvements in broadband technologies and the growth of Internet backbones have expanded the possibilities for where data centers can be located and how they can be used. Server virtualization was only the first step toward the virtualization of data centers. As virtualization technologies continue to advance and develop, industry analysts predict that the entire data center may eventually become virtualized.

"In a virtual environment, time-honored techniques like passive standby systems are a thing of the past because administrators will have the power of near-instant provisioning of virtual machines should one physical system go down.

So even though two machines are in full active mode, one can always handle the workload of the other in case of failover, so the enterprise gains a more efficient use of its infrastructure." (Cole, 2009)

The Cloud is also playing an important role in the future of data centers. Cloud systems will work well with modular, containerized solutions by allowing cloud service providers to scale capacity up or down easily as demand increases or decreases.

Cloud technologies will continue to advance, allowing containerized systems to communicate with one another automatically, provision and de-provision resources, and move data and computing resources around the globe to the most appropriate locations based on demand.

There is an opportunity for data center resource usage to reach a true utility-level functionality, enabling businesses to access resources as needed.

Orchestration software is expected to play a much larger role in data centers by handling documented and repeatable processes that would otherwise be performed by people. This will result in further cost savings and reduced resolution times.

The potential development of programs capable of learning processes and creating new ones through artificial intelligence (AI) is also being researched and developed, further paving the way for greater automation. (CloudBzz, 2011)

Conclusion

Modular and containerized data centers are instrumental in achieving the key design objectives of fourth-generation data centers. With a greater focus on ease of scalability, reduced capital and operating expenses, improved energy efficiency, and support for green initiatives, fourth-generation data centers are well positioned to achieve these goals.

As technology has progressed over the past several decades, business demands on technology have continued to increase. Although it is impossible to predict exactly what the future will bring, data centers can be expected to continue evolving, becoming increasingly cost-effective, automated, and capable.

Bibliography

  • The New Future of Data Centers. (2010, April/May). Focus DatacenterDynamics, pp. 19–20.
  • What Will a Next Generation Data Center Look Like? (2010, June 2). Retrieved October 19, 2011, from IO Data Centers: http://www.odatacenters.com/blog/tag/nxt-generation-data-center/
  • CloudBzz. (2011, January 3). A Vision of the Future Cloud Data Center. Retrieved October 19, 2011, from CloudBzz: http://www.cloudbzz.com/a-vision-of-the-future-cloud-data-center/
  • Cole, A. (2009, May 4). The Three Factors Shaping the Future of the Data Center. Retrieved October 19, 2011, from IT Business Edge: http://www.itbusinessedge.com/cm/community/features/articles/blog/the-three-factors-shaping-the-future-of-the-data-center/?cs=32327
  • Coles, M. B. (2011). Modular/Container Data Centers Procurement Guide: Optimizing for Energy Efficiency and Quick Deployment. Lawrence Berkeley National Laboratory.
  • Edwards, J. (2011, March 28). Data Centers: Make Mine Modular. Retrieved October 19, 2011, from ComputerWorld: http://www.computerworld.com/s/article/9215003/Data_centers_Make_mine_modular
  • Hoover, J. N. (2008, March 1). Data Center Best Practices. Retrieved October 19, 2011, from InformationWeek: http://www.informationweek.com/news/206900660
  • HP. (2010). HP Flexible Data Center - A New Approach to Industrialized IT. Hewlett-Packard.
  • HP. (2011). Manifest: The Best Practices for Data Center Planning. Hewlett-Packard.
  • IBM. (2011). Enterprise Modular Data Center: Increase Flexibility While Reducing Costs. Somers: IBM Global Services.
  • Manos, M. (2008, December 2). Our Vision of Generation 4 Modular Data Centers - One Way of Getting It Just Right. Retrieved October 19, 2011, from LooseBolts: http://loosebolts.wordpress.com/2008/12/02/our-vision-for-generation-r-modular-data-centers-one-way-of-getting-it-just-right/
  • SGI. (2011). Next Generation Data Center Infrastructure: ICE Cube Modular Data Center. SGI.